.. csv-table:: :header: "Command Syntax", "Extra information" :widths: 20, 30 " | ``Eastron,Pause`` | ``Eastron,Resume`` "," | ``Pause`` and ``Resume`` refer to the continuous reading of set registers of all connected Eastron modules. | When changing a setting on a specific module, this background register reading must be temporarily halted by calling ``Eastron,Pause`` first. | All commands are case insensitive. " " | ``Eastron,SetBaud,[,]`` | ``Eastron,SetID,[,]`` "," | The optional ```` parameter indicates the current Modbus address. When not given, the default of address ``1`` is assumed. | Valid node IDs are ``1 ... 247``. | Call ``Eastron,Pause`` before changing settings on the module. | On some modules, like the SDM120, the user must press the button for 3 seconds to enter ``-set-`` mode. | After enabling the ``-set-`` mode, these commands can be given and then the user must press the button for 3 seconds to store the changed settings. | | Changing ID is active immediately, thus the new ID must be used for commands given after changing the ID. | Change of baud rate is only active after the module is power cycled. | | Allowed baud rates: | SDM120 / SDM230: | ``0`` = 2400 baud (default) | ``1`` = 4800 baud | ``2`` = 9600 baud | ``5`` = 1200 baud | | SDM320 / SDM530Y: | ``0`` = 2400 baud | ``1`` = 4800 baud | ``2`` = 9600 baud (default) | ``5`` = 1200 baud | | SDM630 / SDM72 / SDM72V2: | ``0`` = 2400 baud | ``1`` = 4800 baud | ``2`` = 9600 baud (default) | ``3`` = 19200 baud | ``4`` = 38400 baud | | The baud rate parameter can be given either as a value ``0`` ... ``5``, or the exact (supported) baud rate. | | All commands are case insensitive. "