.. include:: ../Plugin/_plugin_substitutions_p09x.repl .. _P092_UVR31_page: UVR31 ===== |P092_typename| |P092_status| Introduction ------------ The UVR31 unit is a single-circuit universal control system. The UVR31 unit is designed for simple solar installations and heating systems (storage charging, domestic hot water preparation) * The DL bus runs at 24 volts. * The data frame consist of 8 bytes (excluding sync). * The data are transmitted @ 50Hz, therefore the transmission of one data set takes about 1.92 seconds. .. image:: P092_UVR31.png Wiring ------ .. image:: P092_24V_Wiring.png Protocol -------- .. image:: P092_UVR31_Protocol.png Setup ----- .. note:: A new device task must be created for each value to be read from the DL bus! .. image:: P092_Setup.png Task settings ~~~~~~~~~~~~~ * **Device**: Heating - DL-Bus (Technische Alternative) * **Name**: Name of the task (example name **ValueN**, where N is a number). * **Enable**: Should the task be enabled or not Sensor ^^^^^^ * **1st GPIO**: DL bus input e.g. **GPIO 14 (D5)** * **DL-Bus Type**: **UVR31** .. note:: The settings for **1st GPIO** and **DL-Bus Type** must be the same for all used DL bus tasks! Inputs ^^^^^^ .. note:: The description of the **Frame data** and the related **Frame bytes** can be found in the section **Protocol**! .. csv-table:: :header: "Frame data", "Frame bytes", "Value", "Index", "Decimals" :widths: 16, 8, 8, 5, 5 "Temp1 ... Temp3", "2 ... 7", "Sensor", "1 - 3", "1" "Output byte", "8", "Digital Output", "", "0" Data acquisition ^^^^^^^^^^^^^^^^ * **Send to controller** 1..3: Check which controller (if any) you want to publish to. All or no controller can be used. * **Interval**: How often should the task publish its value (20..60 seconds is normal). .. note:: Intervall not less than **20 seconds**! The reading of the DL bus happens twice per intervall.