Files
ESPEasy/docs/source/Plugin/P092_ESR21.rst
T
2020-08-22 18:05:12 +02:00

79 lines
2.1 KiB
ReStructuredText

.. include:: ../Plugin/_plugin_substitutions_p09x.repl
.. _P092_ESR21_page:
ESR21
=====
|P092_typename|
|P092_status|
Introduction
------------
The ESR21 unit is a simple solar control.
The ESR21 unit is a differential control that can be used in many ways
* The DL bus runs at 12 volts.
* The data frame consist of 30 bytes (excluding sync and CRC).
* The data are transmitted @ 488Hz, therefore the transmission of one data set takes about 0.67 seconds.
.. image:: P092_ESR21.png
Wiring
------
.. image:: P092_12V_Wiring.png
Protocol
--------
.. image:: P092_ESR21_Protocol.png
Setup
-----
.. note:: A new device task must be created for each value to be read from the DL bus!
.. image:: P092_Setup.png
Task settings
~~~~~~~~~~~~~
* **Device**: Heating - DL-Bus (Technische Alternative)
* **Name**: Name of the task (example name **ValueN**, where N is a number).
* **Enable**: Should the task be enabled or not
Sensor
^^^^^^
* **1st GPIO**: DL bus input e.g. **GPIO 14 (D5)**
* **DL-Bus Type**: **ESR21**
.. note:: The settings for **1st GPIO** and **DL-Bus Type** must be the same for all used DL bus tasks!
Inputs
^^^^^^
.. note:: The description of the **Frame data** and the related **Frame bytes** can be found in the section **Protocol**!
.. csv-table::
:header: "Frame data", "Frame bytes", "Value", "Index", "Decimals"
:widths: 16, 8, 8, 5, 5
"Sensor1 ... Sensor3", "3 ... 8", "Sensor", "1 - 3", "1"
"Ext1 ... Ext6", "9 ... 20", "Ext. Sensor", "1 - 6", "1"
"Output byte", "21", "Digital Output", "", "0"
"Speed step", "22", "Speed step", "", "0"
"Analog output", "23", "Analog output", "", "1"
"Current power", "25,26", "Heat power [kW]", "", "1"
"Heat quantity", "27 ... 30", "Heat meter [MWh]", "", "4"
Data acquisition
^^^^^^^^^^^^^^^^
* **Send to controller** 1..3: Check which controller (if any) you want to publish to. All or no controller can be used.
* **Interval**: How often should the task publish its value (10..60 seconds is normal).
.. note:: Intervall not less than **10 seconds**! The reading of the DL bus happens twice per intervall.