Introduction
|
|
------------
|
|
|
|
The UVR1611 unit is a freely programmable universal control system.
|
|
|
|
The UVR1611 universal controller can be freely programmed using function modules to match any system configuration for heating room management.
|
|
|
|
* The DL bus runs at 12 volts.
|
|
* The data frame consist of 63 bytes (excluding sync and CRC).
|
|
* The data are transmitted @ 488Hz, therefore the transmission of one data set takes about 1.4 seconds.
|
|
|
|
.. image:: P092_UVR1611.png
|
|
|
|
Wiring
|
|
------
|
|
|
|
.. image:: P092_12V_Wiring.png
|
|
|
|
Protocol
|
|
--------
|
|
|
|
.. image:: P092_UVR1611_Protocol.png
|
|
|
|
Setup
|
|
-----
|
|
|
|
.. note:: A new device task must be created for each value to be read from the DL bus!
|
|
|
|
.. image:: P092_Setup.png
|
|
|
|
Task settings
|
|
~~~~~~~~~~~~~
|
|
|
|
* **Device**: Heating - DL-Bus (Technische Alternative)
|
|
* **Name**: Name of the task (example name **ValueN**, where N is a number).
|
|
* **Enable**: Should the task be enabled or not
|
|
|
|
Sensor
|
|
^^^^^^
|
|
|
|
* **1st GPIO**: DL bus input e.g. **GPIO 14 (D5)**
|
|
* **DL-Bus Type**: **UVR1611**
|
|
|
|
.. note:: The settings for **1st GPIO** and **DL-Bus Type** must be the same for all used DL bus tasks!
|
|
|
|
Inputs
|
|
^^^^^^
|
|
|
|
.. note:: The description of the **Frame data** and the related **Frame bytes** can be found in the section **Protocol**!
|
|
|
|
.. csv-table::
|
|
:header: "Frame data", "Frame bytes", "Value", "Index", "Decimals"
|
|
:widths: 16, 8, 8, 5, 5
|
|
|
|
"Sensor1 ... Sensor16", "9 ... 40", "Sensor", "1 - 16", "1"
|
|
"Output A1 ... A7", "41", "Digital Output", "1 - 7", "0"
|
|
"Output A9 ... A13", "42", "Digital Output", "9 - 13", "0"
|
|
"Speed step A1", "43", "Speed step", "1", "0"
|
|
"Speed step A2", "44", "Speed step", "2", "0"
|
|
"Speed step A6", "45", "Speed step", "3", "0"
|
|
"Speed step A7", "46", "Speed step", "4", "0"
|
|
"Current power 1", "48 ... 51", "Heat power [kW]", "1", "2"
|
|
"Current power 2", "56 ... 59", "Heat power [kW]", "2", "2"
|
|
"Heat quantity 1", "52 ... 55", "Heat meter [MWh]", "1", "4"
|
|
"Heat quantity 2", "60 ... 64", "Heat meter [MWh]", "2", "4"
|
|
|
|
Data acquisition
|
|
^^^^^^^^^^^^^^^^
|
|
|
|
* **Send to controller** 1..3: Check which controller (if any) you want to publish to. All or no controller can be used.
|
|
* **Interval**: How often should the task publish its value (10..60 seconds is normal).
|
|
|
|
.. note:: Intervall not less than **10 seconds**! The reading of the DL bus happens twice per intervall.
|