.. csv-table::
|
|
:header: "Command", "Extra information"
|
|
:widths: 20, 30
|
|
|
|
"
|
|
``csecalibrate,[<Voltage>],[<Current>][,<Power>]``
|
|
|
|
Examples:
|
|
|
|
``csecalibrate,229`` to set the current reported voltage to 229V AC
|
|
|
|
``csecalibrate,,0.1`` To set the calibration to report 100 mA as actual current.
|
|
","
|
|
Will set the used calibration reference factors to some known current value.
|
|
For example, if the device using this sensor is plugged into mains power, it may report 200 Volt AC, while it actually is 229V.
|
|
So the value given to this command should then be ``229``, since that's what is supposed to be read.
|
|
|
|
The last two parameters are optional, but their position determines what unit it represents.
|
|
If the setting for current has to be updated, at least 2 parameters must be given of which the first must then be set to ``0``.
|
|
"
|
|
"
|
|
``csereset``
|
|
|
|
","
|
|
Will reset the calibration values to the default values, causing auto-calibration.
|
|
"
|
|
"
|
|
``cseclearpulses``
|
|
|
|
","
|
|
(Added: 2024-01-16)
|
|
Will reset the CF-pulse counter.
|
|
N.B. this also clears the kWh counter as it is derived from the CF-pulse counter.
|
|
"
|