DL bus
|
|
======
|
|
|
|
|P092_typename|
|
|
|P092_status|
|
|
|
|
Introduction
|
|
------------
|
|
|
|
The DL-Bus is used in control units e.g. sold by `Technische Alternative <http://www.ta.co.at/>`_.
|
|
The DL-Bus serves as a bus line for various external sensors and modules.
|
|
The DL-Bus is a bidirectional data line and only compatible with products of Technische Alternative.
|
|
|
|
The data transmission looks as follows:
|
|
* In an infinite loop, a logging data frame is created by the control one after the others on the data line.
|
|
|
|
Up to 4 sensor measured value queries (master/slave) can be made between the individual logging data frames on the DL bus.
|
|
* So that the beginning of a data frame can be detected, a SYNC of 16 high bits is sent before the first data byte.
|
|
* The data transmission is carried out as Manchester code (EXOR linked) with a display clock of 50 or 488Hz (depending on control type).
|
|
|
|
This is necessary to ensure the supply voltage of the logger and DL sensors from the data signal.
|
|
If the receiver is synchronized to the display clock, the correct bit value appears always during the second half period of the data bit (inverted in the first half period).
|
|
|
|
Wiring
|
|
------
|
|
|
|
The DL-Bus consists of 2 wires: DL and GND (sensor ground).
|
|
The power supply for the DL-Bus sensors is supplied via the DL-Bus itself.
|
|
Some DL-Bus devices can/must be powered via a 12V source, e.g. that of the CAN bus (this is explicitly noted in the operating manual of that sensor).
|
|
The cable routing can be star-shaped or serial (from one device to the next).
|
|
Any cable with a cross-section of 0.75 mm2 up to a maximum length of 30 m can be used as a data cable.
|
|
Over 30 m, the use of shielded cables is recommended, which increases the permissible length of the cable to 100 m.
|
|
|
|